EIB-BUS FIRE RESISTANT (PH120)

Technical Features

Cores colour code: Red - White - Black - Yellow  
Conductors: bare copper class 1 CEI EN 60228 (Tab. 9) rule
Insulation: fire resistant silicon rubber CEI 20-11 - CEI EN 50363 rules
Flame barrier: glass tape  
Drain wire: tinned copper  
Shield: aluminium/polyester tape 9/23 µm  
Outer sheat: LSOH termoplastic material M1 quality CEI 20-11 - CEI EN 50363 rules
Outer sheat colour: red RAL 3000  
Flame retardant test: on single core or insulated cable CEI EN 60332-1-2 rule
Smoke's density emitted by cable during the combustion CEI EN 61034-2 rule
Fire resistant test: 120 minutes at temperature of 830 °C CEI EN 50200 rule
LOOP electric resistance: ≤ 75 Ω/km a 20 °C  
Testing voltage core/core: 2000 V x 5’  
Testing voltage core/shield in H2O: 4000 V x 1’  
Capacity core/core: < 100 pF/m a 10 kHz  
Inductance: < 0,85 µH/m a 10 kHz  
Working temperature: (- 40 °C ÷ + 90 °C)  
Short-circuit temperature: 350 °C  
Outer printing: FCT (TN) DIN VDE 4102-12 CE EIB-BUS F.R. 2x2x0.80mm - PH120 - Year /Lot - Progr. Metric  
Bending radius: minimum 15 times of outer diameter  

Tabella Tipo

Cable type MEDIUM Ø OUTER MEDIUM WEIGHT ITEM CODE
 n° x mm²  mm  kg x km  
2x2x0,80 7,3 75 B6602C080FR