| Cores colour code: |
2x... blue-brown 3x.. blue-brown-grey 4x... blue-brown-grey-black 5x... blue-brown-grey-black-black |
|
| Conductors: |
bare copper CLASS 1 |
CEI EN 60228 (Tab. 9) rule |
| Insulation: |
ceramized silicon rubber |
|
| Outer sheat: |
LSOH termoplastic material M1 quality |
CEI 20-11 - CEI EN 50363 rules |
| Outer sheat colour: |
red RAL 3000 |
|
| Smoke density: |
emitted during the combustion |
CEI EN 61034-2 rule |
| Flame retardant test: |
|
IEC 60332-3 rule |
| Fire resistant test: |
60 minutes at the temperature of 830 °C |
CEI EN 50200 rule |
| Electric resistance: |
according to |
CEI EN 60228 (Tab. 9) rule |
| Working voltage: |
450/750 V |
|
| Testing voltage: |
2500 V per 5 minuti |
|
| Working temperature: |
(- 40 °C ÷ + 90 °C) |
|
| Short circuit temperature: |
350 °C |
|
| Outer printing: |
FCT (TN) - EUROSAFE - N. animex Sez. mmq - 450/750 V - BS 6387 CWZ - CEI EN 50200 - PH60 - IEC 60332-3 CE Year |
|