| Cores colour code: |
|
UNEL 00722 (Tab. 8) rule |
| Conductors: |
fine stranded of bare copper |
CEI EN 60228 Cl.5 (Tab. 9) rule |
| Flame protection: |
glass fiber tape 830 °C (-0÷+40 °C) |
|
| Insulation: |
G10 quality thermoplastic rubber |
CEI 20-11 - CEI EN 50363 rules |
| Assembling: |
polyester tape |
|
| Drain wire: |
fine stranded wires of tnned copper 7x0,30 mm |
|
| Shield: |
by aluminium/polyester tape helically wound |
|
| Outer sheath: |
M1 quality polymer compound |
CEI 20-11 - CEI EN 50363 rules |
| Sheath colour code: |
Red RAL 3000 |
|
| Vertical flame retardant test: |
|
CEI EN 60332-1-2 rule |
| GAS emission test: |
during combustion |
CEI EN 50267-2-1 rule |
| Flame retardant test: |
|
CEI EN 50266-2-4 rule |
| Smoke's density: |
during cable combustion |
CEI EN 61034-2 rule |
| Toxicity of gases: |
|
CEI 20-37/7 CEI 20-37/4-0 rules |
| Electric resistance: |
according to |
CEI EN 60228 (Tab. 9) rule |
| Fire resistant test |
Duration 90 min. at 830 °C (-0÷+40 °C) |
CEI EN 50200 (ex CEI 20-36) rule |
| Insulation constant: |
> 100 MΩ x km |
|
| Working voltage: |
0,6/1 kV |
|
| Testing voltage: |
4000 Vc.a. conductors/conductors x 5' - 4000 Vc.a. conductors/shield x 5' |
|
| Working temeprature: |
(- 40 °C ÷ + 90 °C) |
|
| Short circuit temeprature: |
250 °C |
|
| Outer printing: |
BERICA CAVI S.P.A. (VI) FIRE RESISTANT ALARM CEI 20-22 III cat. C CEI 20-45 PH 90 P.Q.A. CE 0,6/1 kV Nr. cond by cross section Year/Lot |
|
| Bending radius: |
cable outer diameter x 10 |
|