| Conductors: |
bare copper |
CEI EN 60228 (Tab. 9) rule |
| Insulation: |
fire resistant silicon rubber |
|
| Fire barrier: |
glass tape |
|
| Colour code: |
different colour |
|
| Outer sheath: |
LSOH termoplastic material M1 quality |
CEI 20-11 - CEI EN 50363 rules |
| Outer sheath colour: |
Red RAL 3000 |
|
| Flame retardant test: |
on single wire or insulated core |
CEI EN 60332-1-2 rules |
| Smoke density: |
emitted from cables during the combustion |
CEI EN 61034-2 rule |
| Fire resistant test: |
30 minutes at temperature of 830 °C |
CEI EN 50200 rule |
| Electric resistance: |
|
CEI EN 60228 (Tab. 9) rule |
| Working voltage: |
450/750 V |
|
| Testing voltage: |
2500 V |
|
| Working temperature: |
(- 40 °C ÷ + 90 °C) |
|
| Short circuit temperature: |
350 °C |
|
| Outer printing: |
FCT (TN) TVCC CABLE FIRE RESISTANT RG 59 B/U + Nr. cond. x cross sect. x/G Sez. CE Year/Lot |
|
| Bending radius: |
minimum 10 times of outer diameter |
|
| Variant: |
with armouring |
|