FIRE RESISTANT TVCC CABLE (PH30)

Technical Features

Conductors: bare copper CEI EN 60228 (Tab. 9) rule
Insulation: fire resistant silicon rubber  
Fire barrier: glass tape  
Colour code: different colour  
Outer sheath: LSOH termoplastic material M1 quality CEI 20-11 - CEI EN 50363 rules
Outer sheath colour: Red RAL 3000  
Flame retardant test: on single wire or insulated core CEI EN 60332-1-2 rules
Smoke density: emitted from cables during the combustion CEI EN 61034-2 rule
Fire resistant test: 30 minutes at temperature of 830 °C CEI EN 50200 rule
Electric resistance: CEI EN 60228 (Tab. 9) rule
Working voltage: 450/750 V  
Testing voltage: 2500 V  
Working temperature: (- 40 °C ÷ + 90 °C)  
Short circuit temperature: 350 °C  
Outer printing: FCT (TN) TVCC CABLE FIRE RESISTANT RG 59 B/U + Nr. cond. x cross sect. x/G Sez. CE Year/Lot  
Bending radius: minimum 10 times of outer diameter  
Variant: with armouring  

Cable type

TYPE MEDIUM Ø OUTER MEDIUM WEIGHT ITEM CODE
 n° x mm²  mm  kg x km  
ELVOX (RG 59+3x1+9x0,50) 15,5 316 B41VCT4FR
URMET (RG 59+2x0,75+6x0,50+6x0,35) 14,6 290 B41VCT5FR
TELECAMERE
(Telecameras) RG 59+2x0,75 12,6 191 B41TLC3FR
(Telecameras) RG 59+2x1 13,2 207 B41TLC4FR
(Telecameras) RG 59+2x1,5 13,7 225 B41TLC2FR
(Telecameras) RG 59+2x1,5+4x0,22 12,8 205 B41TLC6FR